Testing of Reactor RTOS-110-400-0,5 UKhL1
Reactor RTOS-110-400-0,5 UKhL1 was tested under standardized lightning impulse voltages lasting for 1.2/52 μs, 15 pulses of positive and negative polarity (each). The magnitude of test voltage was equal to 485–490 kV.
The reactor was tested under commercial-frequency AC voltage with exposure to it for standardized time interval of 1 minute. The magnitude of test voltage was equal to (230 ± 1.0) kV.
Conclusions: Reactor RTOS-110-400-0,5 UKhL1 meets the requirements of items 5.1.1, 5.2.1, 5.4.1 of GOST 1516.3-96.